Temperature Curve Triple Independent

The Temperature Curve Triple Independent module holds three temperature-to-speed profiles and lets you pick between them from Home Assistant with a select entity. Nothing is shared between the profiles. Each one carries its own five temperature points, its own five speeds, and its own source sensor.

That last part is what separates it from every other temperature module on this board. One profile can follow a heat pump’s flow temperature while another follows a room air sensor imported from Home Assistant, and a third can run inverted so the fans speed up as the temperature falls.

Choose this module when your profiles differ in more than aggressiveness. The typical case is one board serving several operating modes: a heat pump that heats in winter and cools in summer wants a rising curve on 28 to 50 C flow water, a falling curve on 8 to 20 C flow water, and a gentle circulation curve on room air for when the pump is idle. Three different bands and two different sensors is exactly what a shared axis cannot express.

If your three profiles use the same breakpoints and the same sensor and differ only in how hard they react, use Temperature Curve Triple instead. It does that job with 27 Home Assistant entities against this module’s 37. For two profiles with separate axes, see Temperature Curve Dual. For a single fixed curve, see Temperature Curve. The modules overview has a comparison table.

The module does not decide which profile is active. Profile selection is just a select entity; the automation logic lives in Home Assistant.

Each profile names the sensor it reads through curve_a_sensor_id, curve_b_sensor_id and curve_c_sensor_id. Leaving all three at the default gives single-sensor behaviour: every profile follows the onboard HDC1080. Point one at any other sensor in your config, including a platform: homeassistant sensor pulled in from Home Assistant.

sensor:
- platform: homeassistant
id: hp_flow_temperature
entity_id: sensor.heat_pump_flow_temperature
- platform: homeassistant
id: ambient_air_temperature
entity_id: sensor.living_room_temperature
substitutions:
curve_a_sensor_id: "hp_flow_temperature"
curve_b_sensor_id: "ambient_air_temperature"
curve_c_sensor_id: "hp_flow_temperature"

Giving an imported sensor an id but no name keeps it internal. It is an input to the curve, not an entity worth publishing back to Home Assistant.

The module is evaluated on a fixed 10 second interval rather than from a sensor’s on_value trigger. With three possible sources, an on_value trigger would only ever fire for one of them, so the interval is what keeps every profile responsive.

A sensor reads NAN whenever it has no value, which for a platform: homeassistant sensor happens while the Home Assistant entity is unavailable, while HA restarts, or simply before the first state arrives. A brief NAN is normal and must not disturb the fans.

The module holds the last good reading for 60 seconds and keeps controlling from it. If the sensor has still not recovered by then, it triggers the failsafe. In hold mode the 60 second window does not expire; control simply continues from the last good reading until the sensor returns. Entry into the hold, expiry into the failsafe (or the fault condition persisting, in hold mode), and recovery are each logged at warning level.

Switching profiles discards the held value. Holding one profile’s flow temperature and feeding it into another profile’s ambient curve would produce a plausible looking but wrong speed.

The module never sorts your points at runtime. For every profile, point 1 must be the coldest and point 5 the warmest.

Speeds are a different matter from the axis. A profile whose speed falls as temperature rises is exactly how you drive fans harder as water gets colder in cooling mode. The board logs an informational note and raises the warning sensor so you can see it was noticed, but the profile keeps operating normally. It never triggers the failsafe.

Never invert the temperature axis to get an inverted curve. Enter the temperatures ascending and let the speeds descend:

substitutions:
# Cooling: the AXIS ascends 8 to 20, the SPEEDS descend 100 to 0
curve_c_temp1: "8.0"
curve_c_temp2: "11.0"
curve_c_temp3: "14.0"
curve_c_temp4: "17.0"
curve_c_temp5: "20.0"
curve_c_speed1: "100.0"
curve_c_speed2: "80.0"
curve_c_speed3: "55.0"
curve_c_speed4: "30.0"
curve_c_speed5: "0.0"

The five shared axis_temp1 to axis_temp5 substitutions are replaced by three separate axes. To keep the behaviour you had, copy each axis_tempN value into all three of curve_a_tempN, curve_b_tempN and curve_c_tempN, then change the ones you actually want to differ.

Everything else keeps its name and meaning. The speed substitutions, the profile names, the select entity, the per-fan Auto Control switches and the output sensor are all unchanged, so nothing else in your config has to move.

The number entities do change. The shared module exposes one Temp 1 to Temp 5 block plus speeds named <profile> 1 to <profile> 5. Here every number is profile-scoped and qualified, giving <profile> Temp 1 to <profile> Temp 5 and <profile> Speed 1 to <profile> Speed 5. Home Assistant derives entity_id from the entity name, so the old entities do not carry over. Any dashboard card, automation or history that referenced them has to be repointed once.

Renaming a profile renames its Home Assistant entities

Section titled “Renaming a profile renames its Home Assistant entities”

The module’s internal component IDs are fixed literals and are never built from the name variables, so renaming a profile cannot break curve selection or any lambda inside the firmware.

Home Assistant is the part that does not follow along. HA derives each entity_id from the entity name, not from the ESPHome ID, so changing curve_c_name from Turbo to Cooling renames that profile’s ten number entities in Home Assistant. Any dashboard card, automation, or history that referenced the old names will break.

There is no workaround today; it is tracked upstream as esphome/feature-requests#2119. Pick your profile names when you first set the board up.

VariableDefaultDescription
friendly_name"Fancontroller"Device name prefix for the output sensor
curve_a_name"Normal"Display name for profile A
curve_b_name"Heating"Display name for profile B
curve_c_name"Turbo"Display name for profile C
curve_a_sensor_id"fancontroller_temperature"ESPHome id of the sensor profile A reads
curve_b_sensor_id"fancontroller_temperature"ESPHome id of the sensor profile B reads
curve_c_sensor_id"fancontroller_temperature"ESPHome id of the sensor profile C reads
curve_a_temp1"20.0"Profile A temperature point 1 (C)
curve_a_temp2"25.0"Profile A temperature point 2 (C)
curve_a_temp3"30.0"Profile A temperature point 3 (C)
curve_a_temp4"35.0"Profile A temperature point 4 (C)
curve_a_temp5"40.0"Profile A temperature point 5 (C)
curve_a_speed1"0.0"Profile A fan speed at point 1 (%)
curve_a_speed2"30.0"Profile A fan speed at point 2 (%)
curve_a_speed3"55.0"Profile A fan speed at point 3 (%)
curve_a_speed4"80.0"Profile A fan speed at point 4 (%)
curve_a_speed5"100.0"Profile A fan speed at point 5 (%)
curve_b_temp1"20.0"Profile B temperature point 1 (C)
curve_b_temp2"25.0"Profile B temperature point 2 (C)
curve_b_temp3"30.0"Profile B temperature point 3 (C)
curve_b_temp4"35.0"Profile B temperature point 4 (C)
curve_b_temp5"40.0"Profile B temperature point 5 (C)
curve_b_speed1"0.0"Profile B fan speed at point 1 (%)
curve_b_speed2"10.0"Profile B fan speed at point 2 (%)
curve_b_speed3"30.0"Profile B fan speed at point 3 (%)
curve_b_speed4"60.0"Profile B fan speed at point 4 (%)
curve_b_speed5"90.0"Profile B fan speed at point 5 (%)
curve_c_temp1"20.0"Profile C temperature point 1 (C)
curve_c_temp2"25.0"Profile C temperature point 2 (C)
curve_c_temp3"30.0"Profile C temperature point 3 (C)
curve_c_temp4"35.0"Profile C temperature point 4 (C)
curve_c_temp5"40.0"Profile C temperature point 5 (C)
curve_c_speed1"40.0"Profile C fan speed at point 1 (%)
curve_c_speed2"60.0"Profile C fan speed at point 2 (%)
curve_c_speed3"80.0"Profile C fan speed at point 3 (%)
curve_c_speed4"95.0"Profile C fan speed at point 4 (%)
curve_c_speed5"100.0"Profile C fan speed at point 5 (%)
curve_failsafe_speed"100.0"Fan speed (%) the failsafe commands
curve_failsafe_mode"speed"speed or hold

All three axes default to the same 20 to 40 C band, so a config that sets nothing but the speeds behaves like the shared-axis module.

Leaving curve_failsafe_speed and curve_failsafe_mode at their defaults is exactly the behaviour of every earlier version of this module. hold keeps controlling from the last good reading when the source sensor is gone, and keeps the last commanded speed when the active profile’s axis is unordered. hold falls back to curve_failsafe_speed whenever there is nothing yet to hold, which is the case right after a boot or right after a profile switch.

At boot the module validates all three speed sets and reports the result to the log. The temperature axes are deliberately not checked at boot, only live, because the axis numbers are restorable and editable from Home Assistant, so the configured defaults stop being the values in use after the first boot.

Every 10 seconds it resolves the active profile from the select entity’s index position, not by matching the option string, so renaming a profile in your substitutions cannot break which curve is active. Then it:

  1. Scans all three live temperature axes, raising the warning sensor and logging the offending profile by name if any is unordered. The logging is edge triggered, so a persistent misconfiguration is logged once when it appears and once when it clears, not every 10 seconds.
  2. Reads the active profile’s source sensor, applying the 60 second hold if it is unavailable.
  3. Returns the configured failsafe (curve_failsafe_speed and curve_failsafe_mode) if the active profile’s axis is unordered or the hold has expired.
  4. Otherwise linearly interpolates the active profile’s speeds over its own axis. Below the lowest point it holds the first speed; above the highest point it holds the last speed.

The result drives all four fans, gated per fan by the Auto Control Fan 1 to Fan 4 switches and by any active user override, and clamped by each fan’s safety floor. The floor only applies to non-zero speeds; a commanded 0% always turns the fan off.

EntityTypePurpose
Curve SelectionselectPicks the active profile by name. Remembers its last choice across reboots.
$curve_a_name Temp 1 to 5, $curve_b_name Temp 1 to 5, $curve_c_name Temp 1 to 5number (15)Each profile’s own temperature axis, editable live
$curve_a_name Speed 1 to 5, $curve_b_name Speed 1 to 5, $curve_c_name Speed 1 to 5number (15)Each profile’s own speeds, editable live
Auto Control Fan 1 to 4switch (4)Per-fan enable for automatic control
$friendly_name Curve OutputsensorThe active profile’s computed fan speed (%)
Curve Configuration Warningbinary_sensorFlags an unordered axis on any profile (live) or a dipping speed (at boot)

37 entities in total, ten more than Temperature Curve Triple. That is the price of independent axes, and it is expected.

Entity names are laid out profile-major, so with the names from the example Home Assistant sorts them as Cooling Speed 1..5, Cooling Temp 1..5, Heating Speed 1..5, Heating Temp 1..5, and so on. Each profile is one contiguous block, which makes tuning a profile a straight read down the list.

This block goes in your own configuration, not in the module. See why the assignment lives in the consuming config for the reason. version: 3 is what makes entity grouping work at all; without it, entity grouping has no effect.

web_server:
version: 3
sorting_groups:
- id: grp_temp_curve_triple_ind
name: "Temperature Curve Triple Independent"
sorting_weight: 140
number:
- id: !extend curve_a_temp1
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 10
- id: !extend curve_a_temp2
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 20
- id: !extend curve_a_temp3
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 30
- id: !extend curve_a_temp4
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 40
- id: !extend curve_a_temp5
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 50
- id: !extend curve_a_speed1
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 60
- id: !extend curve_a_speed2
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 70
- id: !extend curve_a_speed3
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 80
- id: !extend curve_a_speed4
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 90
- id: !extend curve_a_speed5
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 100
- id: !extend curve_b_temp1
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 110
- id: !extend curve_b_temp2
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 120
- id: !extend curve_b_temp3
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 130
- id: !extend curve_b_temp4
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 140
- id: !extend curve_b_temp5
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 150
- id: !extend curve_b_speed1
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 160
- id: !extend curve_b_speed2
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 170
- id: !extend curve_b_speed3
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 180
- id: !extend curve_b_speed4
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 190
- id: !extend curve_b_speed5
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 200
- id: !extend curve_c_temp1
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 210
- id: !extend curve_c_temp2
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 220
- id: !extend curve_c_temp3
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 230
- id: !extend curve_c_temp4
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 240
- id: !extend curve_c_temp5
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 250
- id: !extend curve_c_speed1
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 260
- id: !extend curve_c_speed2
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 270
- id: !extend curve_c_speed3
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 280
- id: !extend curve_c_speed4
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 290
- id: !extend curve_c_speed5
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 300
select:
- id: !extend curve_select
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 310
switch:
- id: !extend auto_control_fan1
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 320
- id: !extend auto_control_fan2
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 330
- id: !extend auto_control_fan3
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 340
- id: !extend auto_control_fan4
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 350
sensor:
- id: !extend curve_output_value
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 360
binary_sensor:
- id: !extend curve_config_warning_sensor
web_server:
sorting_group_id: grp_temp_curve_triple_ind
sorting_weight: 900

Pair the Curve Selection select with a Home Assistant automation driven by your heat pump’s operating mode. Note that this uses select.select_option rather than switch.turn_on, and that the option value must match the profile name you configured.

automation:
- alias: "Radiator fans follow the heat pump into cooling mode"
trigger:
- platform: state
entity_id: sensor.heat_pump_operating_mode
to: "cooling"
action:
- service: select.select_option
target: { entity_id: select.my_fancontroller_curve_selection }
data:
option: "Cooling"

See examples/with-temperature-curve-triple-independent-rev-3.1.yaml for a complete configuration.