Stall Guard

The Stall Guard module detects when a fan is commanded to run but reports 0 RPM — a stall condition caused by mechanical blockage, bearing failure, or insufficient starting voltage. When a stall is detected, the module progressively raises the fan’s PWM output to attempt recovery and flags a persistent warning in Home Assistant so you know something went wrong.

Use Stall Guard when fan reliability matters — server cooling, network closets, or any unattended installation where a stuck fan could cause overheating. The module is passive until a problem occurs: it monitors RPM in the background and only intervenes when a fan stops spinning unexpectedly.

See the modules overview for a comparison of all available modules.

Stall Guard cooperates with all temperature control modules (Temperature PID, Temperature Linear, Temperature Curve) through a safety floor mechanism.

When Stall Guard detects a stall and starts recovery, it sets a per-fan safety floor — a minimum speed that temperature modules will not go below. This prevents the temperature module from fighting the stall recovery by lowering the fan speed back down.

How the safety floor works:

  1. Fan stalls → Stall Guard raises the fan speed and sets the safety floor to the new value
  2. Temperature module runs its normal calculation (e.g., 30%)
  3. Temperature module sees the safety floor (e.g., 45%) and uses the higher value
  4. Result: fan runs at 45%, the stall recovery value

When the fan is turned OFF (either manually or because temperature dropped below the off threshold), the safety floor is ignored — off always means off. On the next check, Stall Guard automatically clears the stall state and resets the floor for that fan. No manual clear needed.

You can also press Clear Stall Warnings at any time to manually reset all stall states and floors.

The module accepts these substitution variables in the packages: block:

VariableDefaultDescription
friendly_name"Fancontroller"Device name prefix for all HA entities
stall_guard_interval"5s"How often to check each fan’s RPM
stall_guard_grace_ticks"2"Initial value for Grace Ticks (adjustable at runtime via HA)
stall_guard_step_pct"1"Initial value for Step % (adjustable at runtime via HA)
stall_guard_min_rpm"1"Initial value for Min RPM (adjustable at runtime via HA)

The stall_guard_grace_ticks, stall_guard_step_pct, and stall_guard_min_rpm substitutions set the initial values for the corresponding Home Assistant number entities. Once the device boots, users can adjust these values at runtime through the Home Assistant UI — changes persist across reboots.

These parameters can be adjusted at runtime through Home Assistant without reflashing:

EntityDefaultRangeDescription
Stall Guard Min RPM10–1000RPM threshold below which a fan is considered stalled. Default of 1 detects complete standstill. Set higher (e.g., 200) to catch fans spinning too slowly to move air
Stall Guard Step %11–20Percentage to raise fan speed each tick during recovery
Stall Guard Grace Ticks21–20Consecutive low-RPM checks before declaring a stall (effective grace period = interval × ticks)
EntityDefaultDescription
Fan 1 Stall GuardONEnable/disable stall detection for fan 1
Fan 2 Stall GuardONEnable/disable stall detection for fan 2
Fan 3 Stall GuardONEnable/disable stall detection for fan 3
Fan 4 Stall GuardONEnable/disable stall detection for fan 4

All runtime settings use restore_value / restore_mode — changes made in the Home Assistant UI persist across reboots.

One per fan. Shows ON (problem detected) when a stall is active, OFF when clear.

EntityDevice ClassDescription
Fan 1 StallproblemStall detected on fan 1
Fan 2 StallproblemStall detected on fan 2
Fan 3 StallproblemStall detected on fan 3
Fan 4 StallproblemStall detected on fan 4

These are ideal triggers for Home Assistant automations — send a notification when any stall sensor turns on.

One per fan. Shows "OK" when clear, or a message like "Fancontroller Fan 1 stall - raised to 45%" during active stall recovery.

EntityDescription
Fan 1 Stall MessageHuman-readable stall status for fan 1
Fan 2 Stall MessageHuman-readable stall status for fan 2
Fan 3 Stall MessageHuman-readable stall status for fan 3
Fan 4 Stall MessageHuman-readable stall status for fan 4
EntityDescription
Clear Stall WarningsResets all stall flags, messages, and safety floors to OK. Does not change fan speed — the fan continues at whatever speed recovery raised it to, but temperature modules can now lower it freely.
EntityRangeDescription
Stall Guard Min RPM0–1000 RPMRPM threshold for stall detection
Stall Guard Step %1–20%Speed increase per recovery tick
Stall Guard Grace Ticks1–20Low-RPM checks before declaring stall
EntityDescription
Fan 1–4 Stall GuardEnable/disable stall detection per fan
  1. Every stall_guard_interval, the module checks each enabled fan
  2. If a fan is commanded ON but reports RPM below stall_guard_min_rpm, a grace counter starts
  3. After stall_guard_grace_ticks consecutive low-RPM readings, the module declares a stall and immediately begins recovery
  4. On that tick and every tick thereafter, it raises the fan speed by stall_guard_step_pct percent (capped at 100%) and sets the safety floor to that value
  5. The stall warning persists even if the fan recovers — this is intentional so you investigate the cause
  6. If the fan is turned OFF, the stall state and safety floor auto-clear for that fan
  7. Press Clear Stall Warnings in Home Assistant to manually reset all fans

Monitor all 4 fans with default settings (10-second grace period, 1% step-up per tick):

packages:
stall_guard:
url: https://github.com/zeroflow/wifi-fancontroller
ref: main
files:
- path: modules/stall_guard.yaml
vars:
friendly_name: "My Fan Controller"

Only fans 1 and 2 connected, more aggressive recovery:

packages:
stall_guard:
url: https://github.com/zeroflow/wifi-fancontroller
ref: main
files:
- path: modules/stall_guard.yaml
vars:
friendly_name: "Server Rack"

After flashing, disable Fan 3 and Fan 4 stall guard switches and set Step % to 2 in the Home Assistant UI.

Stall Guard works cooperatively with any temperature module (except RPM PI Control). The temperature module controls fan speed based on temperature, while Stall Guard monitors for stalls and sets a safety floor during recovery. No extra configuration needed — include both and they coordinate automatically:

packages:
hardware:
url: https://github.com/zeroflow/wifi-fancontroller
ref: main
files: [hardware-rev-3.1.yaml]
temperature:
url: https://github.com/zeroflow/wifi-fancontroller
ref: main
files:
- path: modules/temperature_linear.yaml
vars:
friendly_name: "NAS Cooling"
stall_guard:
url: https://github.com/zeroflow/wifi-fancontroller
ref: main
files:
- path: modules/stall_guard.yaml
vars:
friendly_name: "NAS Cooling"

After flashing, set Step % to 2 in the Home Assistant UI for more aggressive recovery.

During normal operation, Temperature Linear has full control. If a fan stalls, Stall Guard raises the safety floor so Temperature Linear won’t reduce speed below the recovery value. When the temperature drops enough to turn fans off, the safety floor auto-clears.

  1. Disable unused fans — disable the Fan X Stall Guard switch in Home Assistant for fan ports with nothing connected, otherwise you’ll get false stall warnings
  2. Tune the grace period — the effective grace period is interval × ticks. The default of 5s × 2 = 10 seconds prevents false triggers during normal speed changes. Increase for fans that spin down slowly
  3. Watch the text sensors — the stall message shows the current recovery speed percentage, which tells you how far the module had to raise the fan to attempt recovery
  4. Create HA automations — use the binary sensors as triggers for notifications (e.g., send a push notification when Fan 1 Stall turns on)
  5. Clear warnings after investigating — the warnings are intentionally persistent. After you’ve checked the fan, press Clear Stall Warnings to reset
  6. Adjust step size for your fans — adjust the Stall Guard Step % number entity in Home Assistant to 2 or higher for fans that need a bigger kick to start spinning
  7. Set a minimum RPM for airflow — some fans spin at very low RPM (100-150) without actually moving air. Set the Stall Guard Min RPM entity to 200 in Home Assistant to treat these as stalled and trigger recovery to a useful speed